Advisories › Rockwell Automation › ICSA-26-244-06

Rockwell Automation Historian ME: 2 CVEs, High 8.0

High 8.0 Oil & gas relevant ICSA-26-244-06 · Published Sep 1, 2026 · Updated Sep 9, 2026

Summary

CISA reports 2 vulnerabilities in Rockwell Automation Series B, Series C. Weakness types: Out-of-bounds Write, Stack-based Buffer Overflow. Successful exploitation of these vulnerabilities could crash the device being accessed; an out-of-bounds write condition may allow remote code execution. Highest CVSS v3 score: 8.0 (High), exploitable from an adjacent network.

What to do: Prioritize: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell Automation's security best practices found at…
Why this matters for oil & gas: Rockwell Automation (ControlLogix, FactoryTalk, PlantPAx) is common on facilities and compressor stations; Affected products include Historian.

At a glance

Vendor
Rockwell Automation
Products
Series B, Series C
CVEs
CVE-2025-12768, CVE-2026-12661
Highest CVSS v3
8.0 CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Highest CVSS v4
–
Known exploited (KEV)
No CVE from this advisory is on the KEV list as of the last refresh
Sectors (per CISA)
Chemical, Critical Manufacturing, Food and Agriculture, Healthcare and Public Health, Water and Wastewater
Deployed
Worldwide
Vendor HQ
United States

Vulnerabilities

CVEWeaknessCVSS v3CVSS v4KEVDescription (from advisory)
CVE-2025-12768Out-of-bounds Write8.0–NoA security issue exists within FactoryTalk® Historian Machine Edition. An attacker with low-level authentication could exploit this vulnerability to achieve remote code execution on the affected device.
CVE-2026-12661Stack-based Buffer Overflow4.5–NoA denial-of-service security issue exists within FactoryTalk® Historian Machine Edition. A network adjacent attacker who is authenticated could send crafted requests to the web interface, resulting in buffer overflow conditions that may cause the device to crash and become unresponsive.

Affected products (2)

Vendor fixes and mitigations (from advisory)

Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.

Sources

This page is generated automatically from the CISA advisory text. It is not a substitute for the vendor's guidance; verify affected versions and fixes at the source before making changes to control systems.

Weekly OT patch digest

Every week: the new ICS advisories that touch oil & gas gear, what they mean, and what to do. Free.

Subscribe free

Opens our signup page on beehiiv, where you enter your email. Unsubscribe anytime.