Advisories › Rockwell Automation › ICSA-26-202-07

Rockwell Automation FactoryTalk Services Platform: 1 CVE, High 7.8

High 7.8 Oil & gas relevant ICSA-26-202-07 · Published Jul 21, 2026

Summary

CISA reports 1 vulnerability in Rockwell Automation FactoryTalk Directory (FTSP). Weakness type: Weak Authentication. Successful exploitation of this vulnerability could allow an attacker to impersonate an authorized user on the FTSP server, resulting in unauthorized access to system configurations. Highest CVSS v3 score: 7.8 (High), not remotely exploitable per its CVSS vector.

What to do: Prioritize: Users using FactoryTalk Services Platform v6.60 should apply either the individual patch (RAID 1158263) or the February 2026 Patch Roll-up, or later update.
Why this matters for oil & gas: Rockwell Automation (ControlLogix, FactoryTalk, PlantPAx) is common on facilities and compressor stations; Affected products include FactoryTalk.

At a glance

Vendor
Rockwell Automation
Products
FactoryTalk Directory (FTSP)
CVEs
CVE-2026-10714
Highest CVSS v3
7.8 CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H
Highest CVSS v4
–
Known exploited (KEV)
No CVE from this advisory is on the KEV list as of the last refresh
Sectors (per CISA)
Critical Manufacturing
Deployed
Worldwide
Vendor HQ
United States

Vulnerabilities

CVEWeaknessCVSS v3CVSS v4KEVDescription (from advisory)
CVE-2026-10714Weak Authentication7.8–NoA security issue exists within FactoryTalk Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to imper…

Affected products (1)

Vendor fixes and mitigations (from advisory)

Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.

Sources

This page is generated automatically from the CISA advisory text. It is not a substitute for the vendor's guidance; verify affected versions and fixes at the source before making changes to control systems.