Rockwell Automation FactoryTalk Services Platform: 1 CVE, High 7.8
Summary
CISA reports 1 vulnerability in Rockwell Automation FactoryTalk Directory (FTSP). Weakness type: Weak Authentication. Successful exploitation of this vulnerability could allow an attacker to impersonate an authorized user on the FTSP server, resulting in unauthorized access to system configurations. Highest CVSS v3 score: 7.8 (High), not remotely exploitable per its CVSS vector.
At a glance
- Vendor
- Rockwell Automation
- Products
- FactoryTalk Directory (FTSP)
- CVEs
- CVE-2026-10714
- Highest CVSS v3
- 7.8 CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H
- Highest CVSS v4
- –
- Known exploited (KEV)
- No CVE from this advisory is on the KEV list as of the last refresh
- Sectors (per CISA)
- Critical Manufacturing
- Deployed
- Worldwide
- Vendor HQ
- United States
Vulnerabilities
| CVE | Weakness | CVSS v3 | CVSS v4 | KEV | Description (from advisory) |
|---|---|---|---|---|---|
| CVE-2026-10714 | Weak Authentication | 7.8 | – | No | A security issue exists within FactoryTalk Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to imper… |
Affected products (1)
- Rockwell Automation FactoryTalk Directory (FTSP): 6.60
Vendor fixes and mitigations (from advisory)
- Mitigation: Users using FactoryTalk Services Platform v6.60 should apply either the individual patch (RAID 1158263) or the February 2026 Patch Roll-up, or later update.
- Mitigation: Users using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell's security best practices. link
- Mitigation: For more information, refer to Rockwell Automation's security advisory SD1786 page. link
Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.